12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

The Condor GLW 4 is an electronic base load changeover controller for compressed air systems managing up to 4 compressors. It equalizes operating hours across the compressor fleet while maintaining target system pressure, reducing mechanical wear and energy consumption through intelligent sequencing. The basic unit mounts on a 35 mm DIN rail; pre-wired enclosure variants (GLW 4-S, GLW 4-SK) include main switch, rotary controls, and indicator lamps.

How does the base load changeover logic work?

The GLW 4 designates one compressor as base load (optionally excluded from rotation) and the remaining units as peak load with cycled changeover. The load changeover interval is adjustable from 0 to 999.9 hours per compressor — when the interval expires, the controller swaps the base load assignment to the next available unit with the lowest hours. A ball valve control mode uses the 4th relay to manage up to 3 compressors via a single pressure-regulated ball valve. Remote release (night shutdown) and timer override inputs allow external system integration.

What pressure sensing and control options are available?

An internal 0–16 bar pressure transducer with quick-connect fitting for 6×1 mm pneumatic tubing provides the primary pressure signal at ±2% full-scale accuracy (max permissible 25 bar). Alternatively, an external 4–20 mA 2-wire transducer can be connected, with 18–21 VDC loop power supplied by the GLW 4. Cut-in and cut-out pressure setpoints are independently programmable per profile, with configurable alarm pressure and delay time triggering the dedicated alarm relay.

How are the timer profiles and compressor monitoring configured?

Up to 6 password-protected timer profiles define operating schedules — each profile assigns start/stop times per day of the week, enabling automatic weekday/weekend pressure strategies. The 3-button graphical LCD simplifies parameter entry; factory defaults allow immediate operation. Four digital inputs accept signals from compressor hour meters, fault contacts, or switching cycle counters, giving the GLW 4 visibility into individual unit health. A V.24/COM interface is present for future PC connectivity (not active in V1.01 firmware).

Condor
Compare

Compressor Sequencing Controller for 4 Compressors, 0–16 Bar | Condor GLW 4

Electronic Compressor Sequencing Control
MPN/Series: GLW 4

Product Specifications

Brand
Condor Pressure Control GmbH
Part Number
GLW 4
Product Type
Compressor Sequencing Controller
Compressor Control
Up to 4 compressors with base/peak load assignment
Pressure Transducer
Internal 0–16 bar (±2% FS), external 4–20 mA input supported
Relay Outputs
4 compressor relays + 1 alarm relay (SPDT, 230 VAC / 5 A AC1)
Timer Profiles
6 programmable profiles with weekday scheduling
Load Changeover Interval
0–999.9 h (selectable per compressor)
Supply Voltage
230 VAC ±10%, 50/60 Hz
Mounting
35 mm DIN rail (EN 50022), IP40