Product Specifications
- Brand
- GESTRA AG
- Part Number
- NRR 2-50, NRR 2-51
- Product Type
- Boiler Water Level Limit Controller
- Series
- SPECTORmodule NRR 2-5
- Control Type
- PI (Proportional-Integral)
- NRR 2-50 Output
- 2 volt-free relay contacts (Open/Close stepping)
- NRR 2-51 Output
- 1 × 4–20 mA continuous + 2 relay alarm contacts (MIN & MAX)
- Input
- NRG level electrodes or NRGT 4–20 mA transmitters
- Supply
- 24 VDC, 4 W
- Display
- 4-digit 7-segment LED, MIN/MAX alarm LEDs
- Mounting
- 35 mm DIN rail (EN 60715)
- Weight
- ~0.2 kg
Product Description
The GESTRA NRR 2-50 and NRR 2-51 are water level limit controllers from the SPECTORmodule family, designed for steam boilers, hot water installations, condensate tanks, and feedwater tanks. Both process level-dependent signals from GESTRA NRG electrodes or NRGT transmitters and provide PI (Proportional-Integral) control with configurable MIN/MAX alarm contacts.
What is the difference between the NRR 2-50 and NRR 2-51?
The two models differ in how they drive the control valve:
| Feature | NRR 2-50 | NRR 2-51 |
|---|---|---|
| Valve Actuation | Electrically actuated | Electro-pneumatically actuated |
| Control Output | 2 relay contacts (Open/Close stepping) | 1 × 4–20 mA continuous |
| Alarm Contacts | 1 changeover (MIN or MAX) | 2 changeover (MIN and MAX) |
| Valve Indication | 2 yellow LEDs (OPEN/CLOSE) | Via 4–20 mA signal |
Choose the NRR 2-50 for motorized electric valves requiring step control; choose the NRR 2-51 for pneumatic or I/P-positioned valves requiring a continuous analog control signal. Both models share the same DIN rail housing, 24 VDC supply, and PI control algorithm.
What sensors are compatible?
Both controllers accept GESTRA NRG 21-.. / NRG 26-21 capacitance level electrodes (3-pole with screen) or NRGT 26-.. / NRGT 26-1 / NRGT 26-2 level transmitters with 4–20 mA output (2-pole with shield). A 4-pole code switch on the front panel selects the input type. Up to three NRS/NRR 2-5x units can be connected in parallel for electrode inputs or in series for transmitter inputs, supporting redundant level monitoring in safety-critical boiler applications.
How is PI control configured?
The controller continuously displays the actual water level as a percentage (0–100% of measuring range) on a 4-digit green LED display. Adjustable PI parameters — proportional band (Pb), integral action time (ti), and setpoint (SP) — are configured via a rotary knob with integrated push-button. The control action can be set for fill control or drain/discharge control. On malfunction, MIN and MAX alarms trigger automatically and the system attempts a restart. An alarm off-delay of 3 seconds prevents nuisance trips from transient level fluctuations.
Resources & Documentation
GESTRA NRR 2-50 / 2-51 | Boiler Level Controller, Stepping & Continuous PI
Product Specifications
- Brand
- GESTRA AG
- Part Number
- NRR 2-50, NRR 2-51
- Product Type
- Boiler Water Level Limit Controller
- Series
- SPECTORmodule NRR 2-5
- Control Type
- PI (Proportional-Integral)
- NRR 2-50 Output
- 2 volt-free relay contacts (Open/Close stepping)
- NRR 2-51 Output
- 1 × 4–20 mA continuous + 2 relay alarm contacts (MIN & MAX)
- Input
- NRG level electrodes or NRGT 4–20 mA transmitters
- Supply
- 24 VDC, 4 W
- Display
- 4-digit 7-segment LED, MIN/MAX alarm LEDs
- Mounting
- 35 mm DIN rail (EN 60715)
- Weight