Product Specifications
- Manufacturer
- Telaire
- Series Name
- Ventostat Series
- Available Models
- T8100, T8200, T8300
- Product Type
- Commercial-Grade CO2 Detector / Transmitter for Demand Controlled Ventilation (DCV)
- CO2 Measurement Range
- 0 to 2000 ppm
- Measurement Accuracy (T8100/T8300)
- ±30 ppm or 3% of reading (400-1250 ppm); ±30 ppm + 5% of reading (1250-2000 ppm)
- Measurement Accuracy (T8200)
- 75 ppm or 10% of reading (whichever is greater)
- Output Signals
- 0-10VDC or 4-20mA (no relay outputs); BACnet output available on select versions
- Model-Specific Design
- T8100: Single Channel Sensor with ABC Logic; T8200: Dual-Channel Optical System; T8300: Single Channel Duct-Mount Sensor with Pitot Tube Kit
- Core Feature
- Patented ABC Logic™ Lifetime Calibration Guarantee
- Optional Features
- Humidity & Temperature Measurement, Scrolling Display, Multiple Enclosure Sizes/Colors
- Enclosure Sizes
- Standard: 81.4mm x 116.4mm; Mini: 81.4mm x 86.4mm
- Compliance
- FCC and CE certified
- Target Applications
- Office Buildings, Conference Rooms, Schools, Retail Spaces, Restaurants, Gymnasiums, Movie Theaters
Product Description
The Telaire Ventostat series carbon dioxide detector is a commercial-grade unit designed for Demand Controlled Ventilation (DCV) in buildings. This approach, which uses CO2 levels as an indicator of occupancy, allows ventilation based upon actual occupancy while still maintaining ASHRAE recommended per-person ventilation rates. By using any model of Telaire Ventostat Series carbon dioxide detector, over-ventilation of buildings can be reduced to save energy costs while still maintaining the highest standards of air quality.
Typical applications for the Telaire Ventostat 8000 series carbon dioxide detector include office buildings, conference rooms, schools, retail space, restaurants, gymnasiums, and movie theaters.
The Telaire Ventostat series carbon dioxide detector is available in three core configurations:
Telaire Ventostat T8100
T8100 models use a single channel sensor using Telaire patented ABC Logic for lifetime calibration. Single channel sensors are used in spaces where there is not full-time occupation (most commercial applications).
Telaire Ventostat T8200
T8200 models use a dual-channel optical system and three-point calibration process for enhanced stability, accuracy and reliability. Used in applications where there is fulltime occupation 24 hours a day.
Telaire Ventostat T8300
T8300 models use a single channel sensor with pitot tube kit for duct measuring of CO2, with ABC Logic enabled.
In addition to differing models, the Ventostat series also has a number of options available including enclosure size, scrolling display, humidity measurement, 0-5V output, BACnet output and enclosure color.
Features
- CO2 measurement range: 0 to 2000 ppm
-
Measurement accuracy (T8100/T8300):
- ±30 ppm or 3% of reading 400-1250 ppm
- ±30 ppm + 5% of reading 1250-2000 ppm
- Measurement accuracy (T8200): 75 ppm or 10% of reading (whichever is greater)
- Standard output signals: 0-10VDC or 4-20mA (no relay outputs)
- Available in single or dual channel models, with BACnet output versions available
- Models available for CO2 only, or combined CO2, humidity and temperature measurement
- Lifetime CO2 calibration guarantee when using ABC Logic™
- Easy installation with multiple mounting options
-
Two available enclosure sizes:
- Standard: 81.4mm x 116.4mm
- Mini: 81.4mm x 86.4mm
- FCC and CE certified
Resources & Documentation
Telaire Ventostat Series CO2 Detector | Commercial DCV HVAC Sensor
Product Specifications
- Manufacturer
- Telaire
- Series Name
- Ventostat Series
- Available Models
- T8100, T8200, T8300
- Product Type
- Commercial-Grade CO2 Detector / Transmitter for Demand Controlled Ventilation (DCV)
- CO2 Measurement Range
- 0 to 2000 ppm
- Measurement Accuracy (T8100/T8300)
- ±30 ppm or 3% of reading (400-1250 ppm); ±30 ppm + 5% of reading (1250-2000 ppm)
- Measurement Accuracy (T8200)
- 75 ppm or 10% of reading (whichever is greater)
- Output Signals
- 0-10VDC or 4-20mA (no relay outputs); BACnet output available on select versions
- Model-Specific Design
- T8100: Single Channel Sensor with ABC Logic; T8200: Dual-Channel Optical System; T8300: Single Channel Duct-Mount Sensor with Pitot Tube Kit
- Core Feature
- Patented ABC Logic™ Lifetime Calibration Guarantee
- Optional Features
- Humidity & Temperature Measurement, Scrolling Display, Multiple Enclosure Sizes/Colors
- Enclosure Sizes
- Standard: 81.4mm x 116.4mm; Mini: 81.4mm x 86.4mm
- Compliance
- FCC and CE certified
- Target Applications
- Office Buildings, Conference Rooms, Schools, Retail Spaces, Restaurants, Gymnasiums, Movie Theaters