12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

The Endress+Hauser RLN42 is a two-channel NAMUR isolating amplifier designed for operation of proximity switches according to EN 60947-5-6 (NAMUR), as well as mechanical contacts with resistive coupling elements. It provides a complete interface between hazardous area sensors and safe-area control systems, with intrinsically safe Ex i circuits approved for Zone 0 (gas) and Zone 20 (dust).

Each channel features a relay changeover output, with direction of action selectable via onboard DIP switches. The built-in line fault detection (LFD) continuously monitors input circuits for line breaks and short circuits, and can be disengaged if not required. If a fault is detected, the relay automatically de-energizes to ensure fail-safe operation.

The RLN42 accepts a universal power supply from 20 to 250 V AC/DC, simplifying installation across different regions and panel designs. With SIL2 certification, it is suitable for use in safety instrumented systems up to SIL2 per IEC61508.

Typical applications include:

  • Intrinsically safe interfacing for NAMUR proximity switches
  • Monitoring of mechanical switch contacts in hazardous areas
  • Point level detection with Liquiphant FTL51B and similar sensors
  • Safety-instrumented systems requiring SIL2-rated signal conditioning

Features

  • Two independent channels
  • Input for NAMUR proximity sensors, floating contacts, or contacts with resistive coupling
  • Relay changeover output per channel
  • Line fault detection (LFD) for wire break/short circuit; disengageable
  • Direction of action selectable via DIP switches
  • Universal power: 20 to 250 V AC/DC
  • SIL2 certified per IEC61508
  • ATEX, IECEx, DNV approvals for hazardous areas
  • Ambient temperature: -40 to 60°C
Endress+Hauser
Compare

NAMUR Isolating Amplifier - Relay Output, Line Fault Detection | E+H RLN42

2-channel NAMUR isolator with relay output and SIL2 certific
MPN/Series: RLN42

Product Specifications

Manufacturer
Endress+Hauser
Product Number
RLN42
Type
NAMUR Isolating Amplifier
Channels
2 channels
Input
NAMUR proximity sensors (EN 60947-5-6), floating contacts, or contacts with resistive coupling
Output
Relay, changeover contact per channel
Line Fault Detection (LFD)
Monitors input circuits for line break and short-circuit; disengageable
Power Supply
20 to 250 V AC/DC
Loop Power Supply
8 V DC
Direction of Action
Selectable via DIP switches
Certifications
SIL2 (IEC61508); ATEX, IECEx II(1)G [Ex ia Ga] IIC, II(1)D [Ex ia Da] IIIC, II3G Ex ec nC IIC Gc; DNV
Ambient Temperature
-40 to 60°C (-40 to 140°F)
Documents
Product Manual , Product Specs
NAMUR Isolating Amplifier - Relay Output, Line Fault Detection | E+H RLN42