12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

This pluggable bushing current transformer snaps directly onto the 3NJ6 switch disconnector, measuring the primary current on a 100 A feeder and converting it to a standard 5 A secondary signal for panel instruments. The 21 mm opening accepts cables up to approximately 25 mm², and the FS 5 limiting factor protects connected meters during short‑circuit events.

Key Specifications

  • 100/5 A ratio: a 100 A primary current produces 5 A on the secondary — direct input for standard ammeters and energy meters.
  • Class 1 accuracy, 1.5 VA burden: sufficient for analogue and digital panel displays in industrial distribution.
  • FS 5 overcurrent limiting factor: the core saturates when primary current reaches 500 A, protecting the connected meter from damage.
  • 21 mm cable opening: accommodates feeder conductors up to approximately 25 mm².
  • Tool‑free mounting: clips directly onto the 3NJ6 switch disconnector frame — no brackets or screws needed.

Technical Specifications

Parameter Value
Product type Bushing current transformer
Transformation ratio 100/5 A
Accuracy / Rated burden Class 1 / 1.5 VA
Overcurrent limiting factor FS 5
Cable opening diameter 21 mm
Degree of protection IP20
Dimensions (W × H × D) 44 × 65 × 30 mm
Net weight approx. 185 g
Compatible device 3NJ6 in‑line switch disconnector
Siemens
Compare

3NJ6920-3BD11 Bushing CT 100/5A, Cl.1, 1.5VA, 21mm – Siemens

100/5A, Cl.1, 1.5VA, 21mm
MPN/Series: 3NJ6920-3BD11

Product Specifications

Brand
Siemens
Part Number
3NJ6920-3BD11
Series
SENTRON
Type
Bushing Current Transformer
Transformation Ratio
100/5 A
Accuracy / Burden
Class 1 / 1.5 VA
Cable Opening Diameter
21 mm
Dimensions (W×H×D)
44×65×30 mm