12 month warranty Request a Quote Technical Support
US

Product Specifications

Product Description

The 4AM3442-5CT10 is a 100VA single-phase control transformer from the Siemens SITAS 4AM series, designed specifically for 440V supply environments where 230VAC control power is required. It delivers 0.43A continuous with 310VA S6 short-time capacity for inrush-heavy loads.

440V Applications

440V three-phase distribution is standard in marine and offshore electrical systems (IEC 60092), many North American heavy-industrial facilities, and regions where the legacy 440/460V network voltage persists. This transformer allows control circuits to run at 230VAC directly from the 440V bus without an intermediate step-down stage. The ±5% primary taps (418/440/462V) provide adjustment margin for site voltage variations.

Construction

The EI 84/42 laminated core delivers 86% efficiency with Class B insulation for 40°C ambient operation. IP00 open-style construction mounts via screws or 35mm DIN rail (EN 60715). Screw-type terminals accept ring or fork lugs. Certified to EN 61558-2-2 and EN 61558-2-6 safety isolating standards with CE, cRUus, and EAC approvals.

Key Decision Parameters

Parameter Value
Rated Power (Continuous) 100 VA
Short-Time Power (S6) 310 VA
Primary Voltage 440 V ±5% (418/440/462 V taps)
Secondary Voltage 230 V
Secondary Current 0.43 A
Frequency 50/60 Hz
Efficiency 86%
Insulation Class Class B (40°C ambient)

Related Products

  1. Siemens 4AM3442-5AT10-0FA1 — Step-down 400V to 230V with 310VA inrush handling
  2. Siemens 4AM3442-8DD40-0FA0 — 208-550V multi-tap primary, dual 115/230V output
  3. Siemens 4AM3442-5AV00-0EA0 — 42V SELV control supply from 400V at 100VA
Siemens

Siemens 4AM3442-5CT10 440V to 230V 100VA Single-Phase Control Transformer

230VAC control from 440V marine and industrial mains
MPN/Series: 4AM3442-5CT10-0FA0

Product Specifications

Brand: Siemens

Part Number: 4AM3442-5CT10-0FA0

Product Type: Single-Phase Control / Safety Isolating Transformer

Series: SITAS 4AM3442

Rated Power: 100 VA

Primary Voltage: 440 V ±5% (418/440/462 V taps)

Secondary Voltage: 230 V

Secondary Current: 0.43 A

Short-Time Power (S6): 310 VA

Frequency: 50/60 Hz