Product Specifications
- Manufacturer
- ICON Process Controls
- Model Number
- 300S Series
- Type
- Submersible Level Transmitter
- Pressure Ranges
- 0-14, 0-20, 0-34, 0-54 ftH2O (to about 23 psi)
- Accuracy
- ±0.5% FS
- Output
- 4-20 mA, 4-20 mA + HART, voltage, RS-485
- Documents
- Product Manual, Product Specs
Product Description
ICON LevelPro 300S is a submersible transmitter for continuous level measurement in corrosive and non-corrosive liquids. It measures the head pressure on a 316L stainless steel diaphragm and is intended for tanks where ultrasonic or radar instruments lose the echo to foam, vapor, turbulence or condensate. The sensor has no moving parts and no float, so the reading follows the liquid head rather than a mechanical element.
Ranges, materials and outputs
Level ranges are 14, 20, 34 and 54 ftH2O, with the 54 ft version reaching about 23 psi. The sensor is submersible. Accuracy is half a percent of full scale. The wetted body and diaphragm are 316L stainless steel, the cable is PTFE jacketed, and the O-ring is Kalrez; the housing is IP68 and NEMA 4X for continuous submersion.
Output choices include 4-20 mA, 4-20 mA with HART, voltage and RS-485, with 24 VDC or 5 VDC supply, 25 mA maximum current draw, -25 to 85 C media temperature, response under 10 ms and long-term stability of one tenth of a percent of full scale per year.
The 300S is not a universal replacement for non-contact level instruments. It needs a vented cable path to atmosphere and a liquid density that is known well enough to convert head pressure into level. For chemical sumps and storage tanks where the cable can be routed and the diaphragm is compatible, it removes the line-of-sight problem that ultrasonic sensors have, provided the tank is vented and the cable gland is above the highest liquid level.
Resources & Documentation
ICON 300S Submersible Level Transmitter for Corrosive Liquids
Product Specifications
- Manufacturer
- ICON Process Controls
- Model Number
- 300S Series
- Type
- Submersible Level Transmitter
- Pressure Ranges
- 0-14, 0-20, 0-34, 0-54 ftH2O (to about 23 psi)
- Accuracy
- ±0.5% FS
- Output
- 4-20 mA, 4-20 mA + HART, voltage, RS-485
- Documents
- Product Manual, Product Specs