1 / 5


Product Specifications
- Manufacturer
- Dwyer Instruments
- Model Number
- GSTA / GSTC
- Type
- Gas Transmitter
- Gases Detected
- CO (0-50 to 0-500 ppm selectable) or NO₂ (0-10 ppm)
- Outputs
- GSTA: 4-20mA, 0-5 VDC, 0-10 VDC; GSTC: BACnet or Modbus over RS-485
- Sensor Life
- 4 years typical
- Coverage Area
- 5,000 to 7,500 sq ft
- Documents
- Product Specs
Product Description
Dwyer GSTA and GSTC gas transmitters monitor CO (gasoline engines) and NO₂ (diesel engines) in parking garages and loading docks. Field replaceable electrochemical sensors with 4-year typical life and 5,000-7,500 sq ft coverage.
GSTA models: field selectable analog outputs with invertible output via dip switch. CO ranges configurable from 0-50 to 0-500 ppm; NO₂ standard 0-10 ppm. GSTC models: BACnet or Modbus over RS-485 for building management controller integration. A-449 remote LCD display (sold separately) enables field calibration. CO accuracy: 2% full-scale; NO₂ accuracy: 3% full-scale. End-of-life indication when sensor replacement needed.
Dwyer Instruments
Gas Transmitter - CO NO2 | Dwyer GSTA/GSTC
Carbon monoxide and nitrogen dioxide gas transmitters