SRD960 vs SRD991: Both SIL 3 and Partial-Stroke Testing, Ex d vs Ex ia

Nov 20, 2026
KY Automation
Selection Guide
Contents [hide]

    A control valve is only as honest as its positioner — the device that closes the loop between the controller demand and the stem actual position. Schneider SRD960 and SRD991 are both digital positioners with SIL 3 capability, partial-stroke testing and HART; the difference is explosion protection, not a safety tier.

    SRD960: Ex d flameproof, SIL 3 and diagnostics

    The SRD960 is the explosion-proof Ex d universal positioner, also available in Ex ia. It supports SIL 3 shutdown functions when applied as a fail-safe single-acting spring-return device, with system-level SIL verification. Partial-stroke testing is available. Diagnostics report friction and valve signature data into the asset-management layer, turning the positioner into a valve health monitor. SIS valves in flameproof areas are its natural fit.

    SRD991: Ex ia intrinsically safe, same safety functions

    The SRD991 is the intrinsically safe Ex ia version. It delivers digital positioning, HART, PROFIBUS PA or FOUNDATION Fieldbus H1, and it also supports SIL 3 shutdown functions and partial-stroke testing. It suits hazardous areas where an intrinsically safe circuit is acceptable and Ex d is not required. A level-control loop without a safety function does not need the shutdown path of either model; specify by area classification and required diagnostics.

    Select by area, not by safety tier

    Start with the hazardous-area classification, not the safety label. An Ex d flameproof requirement points to SRD960. An Ex ia intrinsically safe area points to SRD991. Both support SIL 3 and partial-stroke testing; the safety function does not separate them. Both integrate into the same control-room layer and both can report valve health.

    What does partial-stroke testing actually prove?

    On either model, it proves that the valve can move — stiction, sticking and jamming show up as the stem fails to track the small excursion. It does not prove full-travel seat tightness; that still needs shutdown proof tests, just far less often.

    Supply air requirements

    Neither model tolerates wet, dirty air long-term. Supply air must be dry, clean, oil-free and filtered as specified in the manual, whichever model is selected. Filtration is part of the valve installation, not an alternative to it.