A control valve is only as honest as its positioner — the device that closes the loop between the controller demand and the stem actual position. Schneider SRD960 and SRD991 are both digital positioners with SIL 3 capability, partial-stroke testing and HART; the difference is explosion protection, not a safety tier.
SRD960: Ex d flameproof, SIL 3 and diagnostics
The SRD960 is the explosion-proof Ex d universal positioner, also available in Ex ia. It supports SIL 3 shutdown functions when applied as a fail-safe single-acting spring-return device, with system-level SIL verification. Partial-stroke testing is available. Diagnostics report friction and valve signature data into the asset-management layer, turning the positioner into a valve health monitor. SIS valves in flameproof areas are its natural fit.
SRD991: Ex ia intrinsically safe, same safety functions
The SRD991 is the intrinsically safe Ex ia version. It delivers digital positioning, HART, PROFIBUS PA or FOUNDATION Fieldbus H1, and it also supports SIL 3 shutdown functions and partial-stroke testing. It suits hazardous areas where an intrinsically safe circuit is acceptable and Ex d is not required. A level-control loop without a safety function does not need the shutdown path of either model; specify by area classification and required diagnostics.
Select by area, not by safety tier
Start with the hazardous-area classification, not the safety label. An Ex d flameproof requirement points to SRD960. An Ex ia intrinsically safe area points to SRD991. Both support SIL 3 and partial-stroke testing; the safety function does not separate them. Both integrate into the same control-room layer and both can report valve health.
What does partial-stroke testing actually prove?
On either model, it proves that the valve can move — stiction, sticking and jamming show up as the stem fails to track the small excursion. It does not prove full-travel seat tightness; that still needs shutdown proof tests, just far less often.
Supply air requirements
Neither model tolerates wet, dirty air long-term. Supply air must be dry, clean, oil-free and filtered as specified in the manual, whichever model is selected. Filtration is part of the valve installation, not an alternative to it.