12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

For compact three-phase panels that face high fault currents, the 3VA2063‑6HL32‑0AA0 delivers 85 kA H‑class breaking in a space‑efficient 3‑pole design. Its ETU320 LI trip unit focuses on essential overload and instantaneous protection without extra features that add cost.

Protection Functions

  • Overload (L): Ir = 25…63 A, I²t characteristic, delay tr = 0.5…17 s.
  • Instantaneous (I): Ii = 1.5…12 × In (95…756 A).

No neutral protection, no communication, no ground‑fault — just reliable tripping where it matters.

Technical Specifications

Parameter Value
Rated Insulation Voltage Ui 800 V AC
Rated Operational Voltage Ue 690 V AC
Breaking Capacity Icu @415 V 85 kA (Class H)
Service Breaking Capacity Ics @415 V 85 kA
Making Capacity Icm @415 V 187 kA
Mechanical / Electrical Life 25 000 / 15 000 ops @415 V
Power Loss 1.8 W/pole (hot state), 5.4 W total max
Degree of Protection IP40 (front face)
Ambient Temperature 40 °C to 70 °C (full 63 A rating)
Net Weight 2.141 kg
Standard IEC/EN 60947‑2
Country of Origin Czech Republic

Installation & Application

  • Fixed mount on 35 mm DIN rail; nut keeper kit for secure busbar links.
  • Suited for compact high‑fault industrial distribution boards, motor control centres, and generator panels where three‑phase protection is sufficient.
Siemens
Compare

85kA H-Class 3P 63A MCCB, ETU320 LI, Nut-Keeper – Siemens

690V, IP40, No COMM
MPN/Series: 3VA2063-6HL32-0AA0

Product Specifications

Brand
Siemens
Part Number
3VA2063-6HL32-0AA0
Series
3VA2
Type
Molded Case Circuit Breaker
Number of Poles
3
Rated Current In
63 A
Breaking Capacity @415 V
85 kA (Class H)
Protection
ETU320 LI