The Badger Meter 380DS Impeller BTU System measures thermal energy consumption in hydronic heating and cooling systems. It combines an impeller flow sensor with two precision temperature probes to compute energy based on flow rate and temperature differential.

One RTD probe mounts directly in the flow tee; the second installs on the supply or return line. Available in brass tee sizes from 0.75 to 2 inches, covering flow rates from 1.65 to 157.34 gpm. Accuracy is ±2% of flow rate with ±0.5% repeatability. Fluid temperature range is -6.7°C to 126.7°C.

Standard communication includes BACnet MSTP and Modbus RTU over RS-485. A scaled pulse output is also available for integration with PLCs, counters, or wireless systems. All protocols are field-selectable. RS-485 transmits flow rate, flow total, energy rate, energy total, temperatures, and delta T.

Field configuration is via USB connection and free Windows software. Users set energy units, calculation mode, fluid density, specific heat, pulse scaling, and communication parameters.

Features

  • Integrated flow sensor and dual RTD probes
  • Tee sizes: 0.75 to 2 inches
  • Flow range: 1 to 15 ft/sec
  • ±2% accuracy, ±0.5% repeatability
  • Fluid temperature: -6.7°C to 126.7°C
  • BACnet MSTP and Modbus RTU standard
  • Scaled pulse output
  • Field-configurable via USB
  • Tungsten carbide shaft, stainless steel impeller
  • Minimal connections for simplified installation
Badger Meter
Compare

Impeller BTU System - Flow & Temperature Differential | Badger Meter 380DS

Integrates flow and temperature sensors for energy measureme
MPN/Series: 380DS Series

Product Specifications

Manufacturer
Badger Meter
Product Number
380DS Series
Type
Impeller BTU Meter
Flow Range
1 to 15 ft/sec
Tee Sizes
0.75, 1, 1.25, 1.5, 2 inches
Fluid Temperature
-6.7°C to 126.7°C (20°F to 260°F)
Ambient Temperature
-20°C to 65°C (-4°F to 149°F)
Accuracy
±2% of flow rate
Repeatability
±0.5%
Power
12-35V DC, 12-28V AC
Communication
BACnet MSTP, Modbus RTU (RS-485)
Output
Scaled pulse, open drain
RTD
IEC751 Class B
Materials
Brass tee, stainless steel impeller, tungsten carbide shaft, Ketron bearing, EPDM o-ring, polycarbonate housing
Configuration
Field-configurable via USB and free Windows software
Documents
Product Manual , Product Specs
Impeller BTU System - Flow & Temperature Differential | Badger Meter 380DS