12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

The 3VA2063-5HM36-0AA0 is a compact 3-pole molded case circuit breaker from the Siemens SENTRON 3VA2 series, designed for line and system protection in industrial low-voltage power distribution. Equipped with the ETU330 LIG electronic trip unit, it offers a powerful combination of overload (L), instantaneous short-circuit (I), and ground-fault (G) protection—ideally suited for applications where earth-fault monitoring is essential but communication functions are not required.

Core Protection & Control

  • Overload protection (L): adjustable Ir = 25…63 A, I²t characteristic with tr = 0.5…17 s.
  • Instantaneous short-circuit protection (I): adjustable Ii = 1.5…12 x In.
  • Ground-fault protection (G): adjustable pickup Ig = 0.25…1 x In, with selectable time delay tg = 0.1 s or 0.3 s. Detection by residual current summation across all three phases.
  • No communication function and no additional measurement—a cost-optimized solution for standard system protection.

Technical Specifications

  • Rated Insulation Voltage Ui: 800 V AC
  • Rated Operating Voltage Ue: 690 V AC
  • Ultimate Breaking Capacity Icu: 240 V / 85 kA, 415 V / 55 kA, 440 V / 55 kA, 500 V / 36 kA, 690 V / 2 kA
  • Service Breaking Capacity Ics: 240 V / 85 kA, 415 V / 55 kA, 440 V / 55 kA, 500 V / 36 kA, 690 V / 2 kA
  • Making Capacity Icm: 240 V / 187 kA, 415 V / 121 kA, 440 V / 121 kA, 500 V / 75.6 kA, 690 V / 3 kA
  • Mechanical Life: 25,000 operations; Electrical Life: 15,000 operations (at 415 V AC-1)
  • Full 63 A rating maintained across ambient temperature range of 40 °C to 70 °C
  • Power Loss: 5.4 W total (1.8 W per pole at rated current, hot operating state)
  • Degree of Protection: IP40 (front face, with connected conductors)
  • Net Weight: 2.268 kg; Standard: IEC/EN 60947-2

Installation & Application

  • Mounting: Fixed on standard 35 mm DIN rail, symmetrical clamp terminals for reliable conductor connection.
  • Typical Applications: Industrial power distribution panels, motor control centers, and infrastructure systems requiring 3-pole switching with ground-fault detection. Ideal for schemes where an external CT supplies the ground-fault signal and no remote monitoring is needed.
  • Country of Origin: Czech Republic.
Siemens
Compare

Siemens 3VA2 3-Pole 63A 55kA MCCB, ETU330 LIG Ground-Fault Protection

690V, Clamp, IP40
MPN/Series: 3VA2063-5HM36-0AA0

Product Specifications

Manufacturer
Siemens
Part Number
3VA2063-5HM36-0AA0
Product Type
Molded Case Circuit Breaker
Number of Poles
3
Rated Current In
63 A
Breaking Capacity Icu @415 V
55 kA (Class M)
Protection Type
ETU330 LIG
Terminal
Clamp Connection
Siemens 3VA2 3-Pole 63A 55kA MCCB, ETU330 LIG Ground-Fault Protection