12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

The RTT80 is Schneider Electric's I/A Series temperature transmitter - a dual-channel HART 7 unit that takes RTD or thermocouple inputs and adds SIL 2/3 certification and sensor-health diagnostics.

When do you need two temperature sensors?

On a vessel where a failed sensor stops the line, the RTT80 reads two RTD or TC inputs and averages, differences, or hot-swaps to the backup the moment the primary drifts. The alternative - a single sensor - takes the process down on any failure until someone notices.

Why put SIL 2/3 on a temperature transmitter?

It is TÜV-certified for safety-instrumented loops, so it can sit in a SIL-rated trip without an external certificate. The alternative - a non-SIL transmitter - forces a separate safety relay or excludes temperature from the SIS entirely.

How does it warn before the reading lies?

Drift and corrosion diagnostics catch a sensor going bad before the value corrupts, and 2 kV input-to-output isolation keeps the loop clean. The alternative is a dumb transmitter that fails silently and ships a wrong temperature to the controller.

Schneider Electric
Compare

Temperature Transmitter | Schneider RTT80, Dual RTD/TC, SIL 2/3

Dual-channel, SIL 2/3, hot backup
MPN/Series: RTT80

Product Specifications

Brand
Schneider Electric SE
Part Number
RTT80
Type
Temperature Transmitter
Series
Foxboro RTT80
Input
RTD (2/3/4-wire), TC, ohm, mV
Channels
Dual (average / difference / hot backup)
Safety
SIL 2 / SIL 3 (TÜV)
Communication
HART 7 or Foundation Fieldbus
Accuracy
Pt100 ±0.14 °C / TC(K) ±0.32 °C
Diagnostics
Sensor break/short, drift, corrosion
Enclosure
NEMA 4X / IP66-IP67
Mounting
DIN rail / surface / field