Hazardous-area temperature loops usually force a choice: an intrinsically safe barrier setup for zone wiring, or a flameproof enclosure when the process demands Ex d. LI-24ALW covers both paths from one head, which is why it shows up on hydrogen plants, tank farms and chemical skids alike.

Why carry both Ex ia and Ex d on one transmitter?

Because the wiring philosophy changes with the zone. Intrinsically safe loops let you work on the sensor in Zone 1 or 2 without de-energising, while Ex d is the route when the medium temperature pushes the head into a flameproof enclosure. The same LI-24ALW accepts either cable or direct-mounted sensors, and the intrinsically safe version limits output to Uo=6.6 V, Io=9.8 mA - parameters an engineer can hand straight to the barrier calculation.

What does HART 7 add when the loop already reads correctly?

Re-ranging and diagnostics over the same two wires, instead of opening the cover in a classified area. The transmitter accepts Pt100 through Pt1000, Ni100 or thermocouples, its sensor type and range are programmable, and the analogue output holds 0.05% FSO - for retrofits, that often replaces a fixed-range transmitter plus a separate configurator visit.

APLISENS
Compare

Smart Temperature Transmitter | APLISENS LI-24ALW, 4-20mA HART 7, ATEX Ex ia

ATEX Ex ia + Ex d, SIL2/3
MPN/Series: LI-24ALW

Product Specifications

Brand
APLISENS S.A.
Part Number
LI-24ALW
Type
Smart Temperature Transmitter
Series
LI-24L
Input Sensors
RTD Pt10/Pt50/Pt100/Pt200/Pt500/Pt1000, Ni100, Cu50/Cu100, resistance; thermocouples K/J/S/B/N/T/R/E; mV
Pt100 Range
-200 to 850 degC
Output
4-20 mA with HART 7 protocol
Accuracy
0.05% FSO analogue output
Approvals
ATEX/IECEx intrinsic safety (Ex ia IIC T4-T6), Ex d explosion-proof, SIL2/SIL3
Smart Temperature Transmitter | APLISENS LI-24ALW, 4-20mA HART 7, ATEX Ex ia