Product Specifications
Manufacturer:Fluke Corporation
Product Number:772
Type:Milliamp Process Clamp Meter
mA Measurement (Clamp):0-20.99 mA: 0.2% + 5 counts; 21.0-100.0 mA: 1% + 5 counts
mA Measurement (Test Jacks):0-24 mA: 0.2% + 2 counts
mA Source:0-24.00 mA, 0.2% + 2 counts
mA Simulate:0-24.00 mA, 0.2% + 2 counts
Loop Power:24 V DC output
HART Resistor:250 Ω, switchable
Special Features:Detachable clamp with extension cable, simultaneous measure with loop power
Display:Backlit display
Power:Four AA alkaline batteries
Documents: Product Manual, Product Specs
Product Description
The Fluke 772 Milliamp Process Clamp Meter is designed for troubleshooting 4-20 mA control loops without breaking the circuit. Its remote jaw, connected via extension cable, enables in-circuit measurement while the meter provides sourcing, simulation, and loop power capabilities .
The 772 measures mA via clamp (0-20.99 mA with 0.2% accuracy, 21.0-100.0 mA with 1% accuracy) and via test jacks (0-24 mA with 0.2% accuracy). It sources and simulates 0-24 mA with 0.2% accuracy, and provides 24V loop power for transmitter testing. A switchable 250 Ω HART resistor enables communication with smart transmitters .
The detachable clamp features a measurement spotlight LED to help locate mA signal wires in dark control panels. The meter can simultaneously measure mA in-circuit via the clamp while sourcing mA via the test leads, enhancing troubleshooting efficiency. Electronic zero adjustment eliminates offset errors .
Other features include data hold, percentage span display (0-100%), auto power off, and backlight. The meter ships with TL75 test leads, AC72 detachable clip, TL940 mini hook test leads, soft carrying case, and four AA batteries .
Milliamp Process Clamp Meter - 4-20mA Measurement | Fluke 772
Product Specifications
Manufacturer:Fluke Corporation
Product Number:772
Type:Milliamp Process Clamp Meter
mA Measurement (Clamp):0-20.99 mA: 0.2% + 5 counts; 21.0-100.0 mA: 1% + 5 counts
mA Measurement (Test Jacks):0-24 mA: 0.2% + 2 counts
mA Source:0-24.00 mA, 0.2% + 2 counts
mA Simulate:0-24.00 mA, 0.2% + 2 counts
Loop Power:24 V DC output
HART Resistor:250 Ω, switchable
Special Features:Detachable clamp with extension cable, simultaneous measure with loop power
Display:Backlit display
Power:Four AA alkaline batteries
Documents: Product Manual, Product Specs