Product Specifications
- Brand
- Evoqua Water Technologies
- Part Number
- SFC
- Product Type
- Universal Process Controller
- Control Modes
- Feed Forward, Feedback PI, Compound Loop with Adaptive Setpoint Trim
- Universal Input
- TC (R/S/J/T/K/L/B/N/C), RTD Pt100, DC mA/mV/V
- Analog Output
- 0/4–20 mA, ≤500 Ω, <0.5% FS, Galvanically Isolated
- Measured Parameters
- Free/Total Cl₂, ClO₂, O₃, pH, Redox, Fluoride, Conductivity
- Interfaces
- RS485 (SCADA/OPC), RS232 (Firmware), CAN Sensor/Actuator Bus
- Protection Rating
- IP66
Product Description
The SFC, manufactured under the Wallace & Tiernan brand by Evoqua Water Technologies, is a multi-parameter measuring and dosing controller for potable water, industrial process water, and swimming pool water treatment. Its universal process input accepts thermocouples (types R, S, J, T, K, L, B, N, C), 3-wire Pt100 RTDs, and DC linear signals (0/4–20 mA, 0–50 mV, 0–10 V), enabling direct connection to virtually any water quality sensor without external signal conditioning. Measurable parameters include free and total chlorine, chlorine dioxide, ozone, potassium permanganate, pH, Redox, fluoride, and conductivity — all with automatic temperature compensation.
What control strategies does the SFC support?
Three control modes are available. Single feed forward provides flow-proportional dosing where a flowmeter signal directly determines chemical injection rate. Single feedback closed-loop uses PI control to drive a measured water parameter toward a fixed or remote setpoint. The compound-loop mode combines both — flow-proportional feed forward with residual feedback trim — using an adaptive setpoint algorithm with fuzzy logic that continuously adjusts the trim contribution based on process dynamics. This is the control strategy required for drinking water chlorination where both contact-time flow pacing and residual compliance must be satisfied simultaneously. For motor-driven dosing pumps and actuated valves, the SFC supports positioner linearization with 2, 3, 6, or 11 calibration points.
How does it integrate with plant-wide SCADA?
An RS485 interface with support for a process monitoring system and OPC server connects the SFC to higher-level SCADA, allowing remote setpoint adjustment, measured-value readout, and alarm monitoring from a central control room. An RS232 port is reserved for firmware updates. The CAN sensor/actuator bus enables daisy-chaining of compatible digital sensors and actuators on a single cable, reducing wiring compared to point-to-point analog loops. An SD card provides 30-day trend display for two measured variables with on-screen graphing on the 128 × 64 pixel backlit LCD.
Resources & Documentation
Water Treatment Dosing Controller with Compound-Loop Control & Adaptive Setpoint | Evoqua SFC
Product Specifications
- Brand
- Evoqua Water Technologies
- Part Number
- SFC
- Product Type
- Universal Process Controller
- Control Modes
- Feed Forward, Feedback PI, Compound Loop with Adaptive Setpoint Trim
- Universal Input
- TC (R/S/J/T/K/L/B/N/C), RTD Pt100, DC mA/mV/V
- Analog Output
- 0/4–20 mA, ≤500 Ω, <0.5% FS, Galvanically Isolated
- Measured Parameters
- Free/Total Cl₂, ClO₂, O₃, pH, Redox, Fluoride, Conductivity
- Interfaces
- RS485 (SCADA/OPC), RS232 (Firmware), CAN Sensor/Actuator Bus
- Protection Rating
- IP66