12 month warranty Request a Quote Technical Support
US

Product Specifications

Product Description

When earth-fault protection is a hard requirement and the main supply is solidly grounded, the 3VA2063‑6HM46‑0AA0 steps in. It packs an ETU330 LIG trip unit that combines overload, instantaneous short‑circuit and adjustable ground‑fault detection all in a single compact frame. Tucked into a 4‑pole H‑class design, this 63 A breaker is purpose‑built for industrial panels where every kA counts.

Protection Made Simple

  • Overload (L): Ir = 25…63 A, I²t characteristic, delay tr = 0.5…17 s.
  • Instantaneous (I): Ii = 1.5…12 × In.
  • Earth‑Fault (G): Ig = 0.25…1 × In, time delay tg = 0.1 s or 0.3 s. Detection by summation current formation L+N conductor.
  • Neutral (N): Adjustable OFF or 100% of In.

No communication, no extra measurement functions – just solid system protection without hidden costs.

Technical Specifications

Parameter Value
Rated Insulation Voltage Ui 800 V AC
Rated Operational Voltage Ue 690 V AC
Breaking Capacity Icu @415 V 85 kA (Class H)
Service Breaking Capacity Ics @415 V 85 kA
Making Capacity Icm @415 V 187 kA
Mechanical / Electrical Life 25 000 / 15 000 ops @415 V (10 500 ops @690 V)
Power Loss 1.8 W/pole (hot state), 5.4 W total max
Degree of Protection IP40 (front)
Ambient Temperature 40 °C to 70 °C (full 63 A rating)
Net Weight / Packaging Dims 3.200 kg / 169 × 200 × 145 mm
Standard IEC/EN 60947‑2
Country of Origin Czech Republic

Installation & Application

  • Fixed mount on 35 mm DIN rail, terminal connection.
  • Suited for high‑fault industrial main distribution, motor control centres, and generator panels where 4‑pole control, earth‑fault monitoring and high breaking strength must live under one roof.
Siemens
Compare

85kA 4-Pole 63A MCCB with Earth-Fault & N-Protection, Series 3VA2

85kA, 690V, No COMM
MPN/Series: 3VA2063-6HM46-0AA0

Product Specifications

Brand
Siemens
Part Number
3VA2063-6HM46-0AA0
Series
3VA2
Type
Molded Case Circuit Breaker
Number of Poles
4
Rated Current In
63 A
Breaking Capacity @415 V
85 kA (Class H)
Protection
ETU330 LIG
85kA 4-Pole 63A MCCB with Earth-Fault & N-Protection, Series 3VA2