1 / 5
Product Specifications
- Brand
- Siemens
- Part Number
- 3VA2063-6HM42-0AA0
- Series
- 3VA2
- Type
- Molded Case Circuit Breaker
- Number of Poles
- 4
- Rated Current In
- 63 A
- Breaking Capacity @415 V
- 85 kA (Class H)
- Protection
- ETU330 LIG
Product Description
When the main distribution panel demands an earth-fault protection that can sense residual currents across all four conductors, the 3VA2063‑6HM42‑0AA0 stands out. This 85 kA H‑class breaker packs an ETU330 LIG trip unit that combines overload, instantaneous and configurable ground‑fault detection, all terminated through vibration‑proof screw‑flat connectors for direct busbar integration.
Protection Functions
- Overload (L): Ir = 25…63 A, I²t characteristic, delay tr = 0.5…17 s.
- Instantaneous (I): Ii = 1.5…12 × In (95…756 A).
- Ground‑Fault (G): Ig = 0.25…1 × In, time delay tg = 0.1 s or 0.3 s. Detection by residual current summation across L+N conductors.
- Neutral (N): Adjustable OFF or 100% of In.
No communication function, no extra measurement — just reliable tripping when it matters.
Technical Specifications
| Parameter | Value |
|---|---|
| Rated Insulation Voltage Ui | 800 V AC |
| Rated Operational Voltage Ue | 690 V AC |
| Breaking Capacity Icu @415 V | 85 kA (Class H) |
| Service Breaking Capacity Ics @415 V | 85 kA |
| Making Capacity Icm @415 V | 187 kA |
| Mechanical / Electrical Life | 25 000 / 15 000 ops @415 V (10 500 ops @690 V) |
| Power Loss | 1.8 W/pole (hot state), 5.4 W total max |
| Degree of Protection | IP40 (front face), IP20 (overall) |
| Ambient Temperature | 40 °C to 70 °C (full 63 A rating) |
| Net Weight | 2.731 kg |
| Dimensions (W × H × D) | 140 × 181 × 86 mm |
| Standard | IEC/EN 60947‑2 |
| Country of Origin | Czech Republic |
Installation & Application
- Fixed mount on 35 mm DIN rail; screw‑flat connector (nut keeper kit) provides a secure, low‑resistance busbar termination.
- Suited for high‑fault industrial main distribution boards, motor control centres, and generator panels wherever 4‑pole switching, earth‑fault protection and mechanical resilience are required.
Related Products
Siemens
Compare
85kA 4-Pole MCCB with Ground-Fault & N-Switching, Screw-Flat – Siemens 3VA2
85kA, 690V, IP40
MPN/Series: 3VA2063-6HM42-0AA0
Product Specifications
- Brand
- Siemens
- Part Number
- 3VA2063-6HM42-0AA0
- Series
- 3VA2
- Type
- Molded Case Circuit Breaker
- Number of Poles
- 4
- Rated Current In
- 63 A
- Breaking Capacity @415 V
- 85 kA (Class H)
- Protection
- ETU330 LIG