Product Specifications
- Brand
- Siemens
- Part Number
- 6SL3520-0XK03-0AF0
- Series
- SINAMICS G115D
- Type
- Wall-Mounted Frequency Converter
- Power Rating
- 3 kW
- Rated Voltage
- 480 V 3-Phase AC
- Output Current
- 15.4 A
- Protection Class
- IP65/IP66 / UL Type 4X
- EMC Filter
- Category C2 Integrated
- Overload Capability
- 200% (3s) / 150% (57s)
- Dimensions (W×H×D)
- 425 × 240 × 134 mm
- Frame Size
- FSB
- Ambient Temperature
- -30 to +55°C
Product Description
The 6SL3520-0XK03-0AF0 occupies the 3 kW mid-point of the G115D wall-mounted FSB range, delivering 15.4 A with the full-featured -0AF0 I/O and communication configuration. At 134 mm deep, it shares the shallower enclosure with the 2.2 kW variant — the extra current headroom comes from a higher-rated power stage within the same 425 × 240 mm footprint, making it the sweet spot for installations that need a step above entry-level without the 169 mm depth of the 4 kW unit.
Where does the 3 kW variant fit in the G115D FSB power ladder?
The FSB frame spans 2.2 to 4 kW across three power nodes. The 3 kW / 15.4 A variant is the upper-mid option — it covers the most common IEC motor sizes in building services (3 kW supply and return fans, 3 kW chilled-water pumps, 3 kW cooling-tower fans) without the extra depth and cost of the 4 kW unit. It provides a 30% current margin over the 2.2 kW variant at 11.8 A, which can be decisive when motor nameplate current sits above 12 A.
What overload performance does this drive offer for pump and fan duty?
The drive supports a high-overload (HO) profile: 200% for 3 seconds to clear momentary blockages, 150% for 57 seconds for demand surges, within a 300 s cycle. This profile is engineered for centrifugal loads where torque varies with the square of speed — typical of HVAC pumps, cooling-tower fans, and air-handling units.
Frequently Asked Questions
Can the 3 kW variant run a 4 kW motor if the actual load never exceeds 3 kW?
No. The drive must be sized to the motor's full-load current rating, not the anticipated operating load. A 4 kW IEC motor at 480 V typically draws roughly 7 A at full load — close to the 3 kW drive's rated current — so select the 4 kW / 20.4 A variant instead.
What is the maximum motor cable length without an output reactor?
All G115D variants support motor cable runs up to 15 m without an additional output reactor, covering most distributed pump and fan installations.
Related Products
Resources & Documentation
Siemens 6SL3520-0XK03-0AF0 3kW SINAMICS G115D Wall-Mounted Frequency Converter with IP65 Protection
Product Specifications
- Brand
- Siemens
- Part Number
- 6SL3520-0XK03-0AF0
- Series
- SINAMICS G115D
- Type
- Wall-Mounted Frequency Converter
- Power Rating
- 3 kW
- Rated Voltage
- 480 V 3-Phase AC
- Output Current
- 15.4 A
- Protection Class
- IP65/IP66 / UL Type 4X
- EMC Filter
- Category C2 Integrated
- Overload Capability
- 200% (3s) / 150% (57s)
- Dimensions (W×H×D)
- 425 × 240 × 134 mm
- Frame Size
- FSB
- Ambient Temperature
- -30 to +55°C