Product Specifications
- Manufacturer
- Siemens
- Model Number
- 6SL3230-2YE50-1CB0
- Type
- Frequency Converter (Pump and Fan Drive)
- Input Voltage
- 3 AC 380 to 480 V, +10 / -20 percent, 47 to 63 Hz
- Rated Power
- 160 kW LO; 132 kW HO
- Rated Output Current
- 302 A LO (400 V and 480 V); 250 A HO at 400 V, 240 A at 480 V
- Rated Input Current
- 301 A at 400 V
- Overload
- LO 110 percent for 60 s in 300 s; HO 150 percent for 60 s in 600 s
- EMC Filter
- Integrated Category C3 line filter (C suffix)
- Frame Size
- FSG, forced-air cooling, integrated DC link reactor
- Protection
- IP20 / UL open type
- Communication
- USS, Modbus RTU, BACnet MS/TP (B suffix, on board)
- Control
- Internal PID plus 3 additional PID controllers; multi-pump control of up to 4 pumps
- Regeneration
- No regenerative feedback to supply; no braking resistor dissipation
- Ambient
- -20 to +60 C at 5 cm clearance or -20 to +50 C side by side, derating above 45 C
Product Description
A 160 kW pump station often answers to two masters: the building-management system on its BACnet MS/TP trunk and the water-side SCADA on Modbus RTU. This SINAMICS G120X carries both protocols on board, together with USS for bench setup, through the B communication suffix; no separate communication board is needed.
The 160 kW rating is the low-overload duty at 400 and 480 V three-phase, with a rated output current of 302 A and an input current of 301 A at 400 V. High overload steps down to 132 kW, rated 250 A at 400 V and 240 A at 480 V. Overload is 110 percent for 60 s within a 300 s cycle on LO and 150 percent for 60 s within a 600 s cycle on HO.
Supply is 3 AC 380 to 480 V with plus 10 and minus 20 percent tolerance at 47 to 63 Hz. The C suffix marks an integrated Category C3 line filter, and the 160 kW build sits in frame FSG, which it shares with the 200 kW builds above it. Cooling is forced air, a DC link reactor is integrated, and installation up to 1000 m needs no derating. The enclosure is IP20 / UL open type for mounting inside a control cabinet.
The drive targets pumps, fans and comparable low-dynamic loads in water and wastewater, industrial and building-automation plants. It provides an internal PID controller plus three additional free PID controllers and multi-pump control of up to four pumps. Regenerative energy can neither be returned to the supply nor dissipated through a braking chopper and braking resistor; a duty that needs regeneration therefore belongs to a different drive family.
For the BACnet communication version, the permitted ambient range is minus 20 to plus 60 C with 5 cm side clearance, or minus 20 to plus 50 C for side-by-side mounting, with derating above 45 C. CE marking follows directives 2014/30/EU and 2014/35/EU, with UL and cUL listing. The order-code supplement table defines the environment class and operator-panel options, but a digit-by-digit decoding of the complete order number is not published.
Related Products
Resources & Documentation
Siemens SINAMICS G120X 160kW 380-480V C3 Filtered BACnet Modbus
Product Specifications
- Manufacturer
- Siemens
- Model Number
- 6SL3230-2YE50-1CB0
- Type
- Frequency Converter (Pump and Fan Drive)
- Input Voltage
- 3 AC 380 to 480 V, +10 / -20 percent, 47 to 63 Hz
- Rated Power
- 160 kW LO; 132 kW HO
- Rated Output Current
- 302 A LO (400 V and 480 V); 250 A HO at 400 V, 240 A at 480 V
- Rated Input Current
- 301 A at 400 V
- Overload
- LO 110 percent for 60 s in 300 s; HO 150 percent for 60 s in 600 s
- EMC Filter
- Integrated Category C3 line filter (C suffix)
- Frame Size
- FSG, forced-air cooling, integrated DC link reactor
- Protection
- IP20 / UL open type
- Communication
- USS, Modbus RTU, BACnet MS/TP (B suffix, on board)
- Control
- Internal PID plus 3 additional PID controllers; multi-pump control of up to 4 pumps
- Regeneration
- No regenerative feedback to supply; no braking resistor dissipation
- Ambient