12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

The Siemens 7KT1670 is the direct-connected 80 A variant of the PAC1600 series with S0 pulse output. It wires directly into the three-phase supply without external current transformers, making it the simplest PAC1600 to install for loads up to 80 A. The S0 pulse interface feeds energy data to pulse counters, data loggers, and BMS digital inputs.

Direct 80 A connection — when does this work and when do I need CTs?

With 80 A direct connection, the meter's internal current path carries the full load current through screw terminals sized for conductors up to 25 mm². This works for most branch circuits, small distribution panels, and individual machine supplies. However, the 80 A rating is the maximum continuous current — if your load exceeds 80 A, you must use a CT-connected model (7KT1672 or 7KT1673) with appropriately sized external current transformers. There is no way to extend the 7KT1670's range with external CTs.

What does the S0 pulse interface give me — and what does it not?

The S0 output provides accumulated energy pulses (active and reactive on two separate channels) to external counters. Each pulse equals a fixed energy quantum. This is ideal for: remote totalization via pulse counter, input to a BMS or energy data logger with digital inputs, and simple kWh monitoring without a communication network. What S0 cannot do: transmit instantaneous values (voltage, current, power factor), support remote configuration, or provide alarm/warning flags. For those capabilities, consider the Modbus RTU or M-Bus variants.

Parameter 7KT1670 (80A, S0) 7KT1672 (5A, S0) 7KT1665 (80A, Modbus)
Current Input 80 A direct 5 A via CT 80 A direct
Communication S0 Pulse S0 Pulse Modbus RTU/ASCII
MID Certified No No No
Max Load 80 A direct Unlimited via CT 80 A direct
Data Detail Energy pulses only Energy pulses only Full register access

Frequently Asked Questions

What cable size fits the 80 A direct terminals?

The screw terminals accept conductors up to 25 mm², which is adequate for 80 A continuous current with standard PVC-insulated copper cable. Always follow local wiring regulations for conductor sizing and overcurrent protection upstream of the meter.

Does the 7KT1670 need an auxiliary power supply?

No. Like all PAC1600 three-phase meters, the 7KT1670 is self-powered from the measured voltage — no separate auxiliary supply wiring is needed. The meter powers up as soon as voltage is present on the L-N terminals.

Related Products

  1. Siemens 7KT1668 — M-Bus interface with MID billing compliance for direct 80 A three-phase measurement
  2. Siemens 7KT1664 — M-Bus with MID billing certification for CT-connected 5 A three-phase measurement
  3. Siemens 7KT1667 — M-Bus networked energy monitoring with direct 80 A connection, no MID
  4. Siemens 7KT1666 — Modbus RTU with MID billing certification for direct 80 A three-phase measurement
Siemens
Compare

Siemens 7KT1670 PAC1600 3-Phase Energy Meter — S0 Pulse Output, 80A Direct-Connected

Direct 80 A connection with S0 pulse output for simple energy monitoring setups
MPN/Series: 7KT1670

Product Specifications

Brand
Siemens
Part Number
7KT1670
Product Type
3-Phase Energy Meter
Series
SENTRON PAC1600
Current Input
80 A (direct-connected)
Communication Interface
S0 Pulse Output (IEC 62053-31)
MID Certification
No
Accuracy (Active Energy)
Class 1 (IEC/EN 62053-21)
Nominal Voltage
230 V L-N / 400 V L-L
Frequency
50/60 Hz
Dimensions (L × W × H)
90 × 72 × 63 mm
Weight
360 g
Mounting
DIN Rail
Siemens 7KT1670 PAC1600 3-Phase Energy Meter — S0 Pulse Output, 80A Direct-Connected