12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

For a 240 V site moving to Ethernet, the 6SL3230-3YC30-1UF0 puts PROFINET/EtherNet/IP on the 18.5 kW drive. Same 92 A LO rating, same FSD frame (200 x 472 x 239 mm), IP20 - but the F suffix is the modern machine-network interface, and the 1U keeps DC terminals for braking or a common DC bus.

Running 18.5 kW at 92 A on 200-240 V is the whole appeal of the 3YC low-voltage class: no step-up transformer, no derating, just a drive that bolts into a 240 V panel. The U is unfiltered EMC - fine when the cabinet already provides filtering, or when the installation does not demand a built-in stage.

Where this differs from its siblings: the 1UP0 is the PROFIBUS version for legacy plants, the 0UP0 sheds the DC terminals for a pure PROFIBUS job, and the 1UB0 drops to USS/Modbus for the cheapest serial retrofit. Pick the 1UF0 when the machine network is PROFINET and you still want a brake-resistor landing point.

Siemens
Compare

Siemens 6SL3230-3YC30-1UF0 | SINAMICS G120X 18.5 kW PROFINET EtherNet/IP drive with DC terminals

SINAMICS G120X 18.5kW 200-240V
MPN/Series: 6SL3230-3YC30-1UF0

Product Specifications

Brand
Siemens
Model Number
6SL3230-3YC30-1UF0
Type
SINAMICS G120X general-purpose converter
Series
SINAMICS G120X
Rated Power
18.5 kW
Rated Current
92 A (LO, 110% / 60 s)
Input Voltage
3AC 200-240 V
Communication
PROFINET, EtherNet/IP
DC Terminals
Present
EMC Filter
Unfiltered
Frame Size
FSD
Protection Rating
IP20 (cabinet-mount)
Dimensions
200 x 472 x 239 mm
Siemens 6SL3230-3YC30-1UF0 | SINAMICS G120X 18.5 kW PROFINET EtherNet/IP drive with DC terminals