12 month warranty Request a Quote Technical Support
US

Product Specifications

Product Description

XE03-0AA0 is the final piece of the XE03 communication puzzle — SINAMICS G115D at 3kW fanless FSB with I/O Control. With this PN, XE03 now carries all three G115D communication interfaces. XE03-0AA0 uses digital and analog I/O signals — start/stop via a 24V digital input, speed reference via a 0–10V analog input. No fieldbus, no network configuration, no GSD file. For a standalone pump, a fan array, or a conveyor section that only needs run/stop and a speed pot on the panel door, this is the simplest path to 3kW of fanless distributed drive power.

When does I/O Control make more sense than PROFINET on a 3kW drive?

I/O Control wins when the control architecture is relay-based or when the PLC lacks a fieldbus port. A 3kW fanless drive controlled by I/O is a drop-in replacement for a contactor-plus-overload relay combination — same control wiring, dramatically more functionality. The drive handles ramp-up, ramp-down, overload protection, and speed adjustment without adding a single network device to the control panel. For machine builders shipping to end users who do not have PROFINET-capable maintenance tools, I/O Control also simplifies troubleshooting — any electrician with a multimeter can verify the control signals.

How does XE03-0AA0 differ from XE03-0AF0 and XE03-0AB0?

The hardware is identical — same 3kW fanless FSB drive, same 15.4A overload capacity, same IP65 enclosure. The difference is the communication interface: AA0 uses digital/analog I/O (no fieldbus), AF0 uses AS-Interface (two-wire yellow flat cable), AB0 uses PROFINET (with PROFIsafe and MRP). All three XE03 variants are now confirmed and available — the choice is purely about how the higher-level control system talks to the drive.

Frequently Asked Questions

What control signals does the AA0 interface support?

The I/O Control interface provides digital inputs for start/stop, direction, and fixed-speed selection, plus an analog input (0–10V or 4–20mA) for speed reference. A digital output reports drive status (ready/running/fault). No fieldbus configuration is required — wire the signals and set parameters via the integrated keypad or SD card.

Can this drive be mounted outdoors?

IP65-rated, so it handles dust and water jets directly. However, the electronics are rated for 0–55°C ambient (with derating above 40°C). Direct sunlight on a dark enclosure can push the internal temperature beyond the rated range. A simple sun shield resolves this — no additional cooling needed.

Siemens

SINAMICS G115D 3kW Fanless FSB Distributed Drive with I/O Control 6SL3520-0XE03-0AA0

3kW Fanless I/O Control G115D XE0x
MPN/Series: 6SL3520-0XE03-0AA0

Product Specifications

Brand: Siemens

Part Number: 6SL3520-0XE03-0AA0

Type: Frequency Converter / Distributed Drive

Series: SINAMICS G115D

Power Rating: 3 kW (7.7 A rated / 15.4 A overload)

Voltage: 3-phase 380–480 V

Frame Size: FSB Fanless (425×180×134 mm)

Cooling: Natural Convection

Communication: I/O Control (Digital/Analog Signals)

Protection: IP65

Weight: 7.12 kg