The Allen-Bradley 1489-M is a UL 489 listed thermal-magnetic circuit breaker for branch-circuit protection in control panels — the North-American-listed counterpart to the IEC-only 1492 family, in a 17.5 mm DIN-rail body.

1489-M or 1492-D?

The 1489-M is UL 489 listed for branch circuits, breaking up to 15 kA at 480Y/277V, with C and D curves from 0.5 to 63 A. The 1492-D is UL 1077 supplementary protection, not a listed branch breaker. Choose the 1489-M when the NEC or a local code calls for a listed branch breaker; choose the 1492-D for control and supplementary feeds. The alternative — using a 1492-D on a mains branch — fails the listing requirement.

How much can it actually break?

At 15 kA interrupting it clears a heavy downstream fault that a low-interrupting MCB would weld shut, and the IP20 finger-safe terminals protect the installer on both sides. The alternative — a 10 kA MCB on a high-available-fault bus — may not clear the worst case.

Does it share the 1492 footprint?

It is 17.5 mm wide on the same DIN rail with dual clamp terminals, so it mixes with the 1492 blocks in one panel row. The alternative — a molded-case breaker — needs many times the space for the same pole count.

Resources & Documentation

Allen-Bradley
Compare

Allen-Bradley 1489-M | UL 489 Circuit Breaker, 15 kA, DIN

UL 489 breaker, 0.5–63 A, 15 kA
MPN/Series: 1489-M

Product Specifications

Brand
Rockwell Automation, Inc.
Part Number
1489-M
Type
Thermal-Magnetic Circuit Breaker
Series
1489-M
Standard
UL 489, IEC 60947-2
Current
0.5…63 A
Interrupting
15 kA
Trip Curves
C / D
Mounting
DIN Rail, IP20