12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

When a high-fault panel simply needs a solid 4-pole main breaker without extra protection layers, the 3VA2063‑6HL46‑0AA0 fits right in. It combines 85 kA H-class breaking with an ETU320 LI trip unit, delivering essential overload and instantaneous short-circuit protection through straightforward clamp terminals.

Protection Functions

  • Overload (L): Ir = 25…63 A, I²t characteristic, delay tr = 0.5…17 s.
  • Instantaneous (I): Ii = 1.5…12 × In (95…756 A).
  • Neutral (N): Adjustable OFF or 100% of In.

No communication, no ground-fault monitoring—just reliable tripping when it counts.

Technical Specifications

Parameter Value
Rated Insulation Voltage Ui 800 V AC
Rated Operational Voltage Ue 690 V AC
Breaking Capacity Icu @415 V 85 kA (Class H)
Service Breaking Capacity Ics @415 V 85 kA
Mechanical / Electrical Life 25 000 / 15 000 ops @415 V
Power Loss 1.8 W/pole (hot state), 5.4 W total max
Degree of Protection IP40 (front face)
Ambient Temperature 40 °C to 70 °C (full 63 A rating)
Net Weight 2.938 kg
Standard IEC/EN 60947-2
Country of Origin Czech Republic

Installation & Application

  • Fixed mount on 35 mm DIN rail; clamp terminal connection for straightforward wiring.
  • Suited for high-fault industrial main distribution boards, motor control centres, and generator panels where 4-pole switching is required without advanced protection features.
Siemens
Compare

4-Pole 85kA 63A MCCB, ETU320 LI Terminal, Series 3VA2 – Siemens

85kA, 690V, IP40
MPN/Series: 3VA2063-6HL46-0AA0

Product Specifications

Brand
Siemens
Part Number
3VA2063-6HL46-0AA0
Series
3VA2
Type
Molded Case Circuit Breaker
Number of Poles
4
Rated Current In
63 A
Breaking Capacity @415 V
85 kA (Class H)
Protection
ETU320 LI
Terminal
Clamp Connection
4-Pole 85kA 63A MCCB, ETU320 LI Terminal, Series 3VA2 – Siemens