12 month warranty Request a Quote Technical Support
Sign In

Product Specifications

Product Description

When the cabinet needs C2 EMC compliance, do I add an external filter?

Dedicated industrial supplies — water-treatment buildings, HVAC plant rooms — fall under EMC Category C2. This unit ships with the C2 filter built in and tested at the factory, so there is no external filter module to source or wire — an unfiltered variant would push that cost and a commissioning step onto your build.

Does my PROFIBUS DP network connect without a gateway?

PROFIBUS DP is onboard, so the drive drops onto an existing Profibus network as a standard node — no communications gateway. For industrial Ethernet use the PROFINET/EtherNet/IP variant; for serial or building buses use the USS/Modbus/BACnet variant.

What overload rating applies to pump and fan duty?

Pump and fan loads are variable-torque, so the drive is rated at Low Overload: 110% of rated current for 60 s. At 1.1 kW that is 3.0 A continuous with short-term headroom for start-up surges, in a 73 x 232 x 209 mm IP20 frame that mounts directly in the cabinet.

Siemens
Compare

Siemens 6SL3230-3YE12-0AP0 | SINAMICS G120X 1.1 kW Drive with PROFIBUS DP, C2 EMC

1.1kW C2 PROFIBUS Drive
MPN/Series: 6SL3230-3YE12-0AP0

Product Specifications

Brand
Siemens
Model Number
6SL3230-3YE12-0AP0
Type
SINAMICS G120X Frequency Converter
Series
SINAMICS G120X
Rated Power
1.1 kW (Variable Torque)
Rated Current
3.0 A
Supply Voltage
3 AC 380-480 V, 47-63 Hz
Frame Size
FSA (73 x 232 x 209 mm)
Protection Rating
IP20 / UL Open Type
EMC Filter
Integrated C2
DC Terminals
No
Communication
PROFIBUS DP
Overload Capacity
110% for 60 s (Low Overload)
Output Frequency
0-550 Hz
Siemens 6SL3230-3YE12-0AP0 | SINAMICS G120X 1.1 kW Drive with PROFIBUS DP, C2 EMC